burst impulse | 1 kv, signal cable, according to iec/en 61131-2, level 3 1 kv, smartwire-dt cable, according to iec/en 61131-2, level 3 2 kv, supply cable, according to iec/en 61131-2, level 3 |
||
time delay at signal exchange - min | 0 ms | ||
supply voltage at ac, 50 hz - max | 0 vac | ||
supply voltage at ac, 50 hz - min | 0 vac | ||
time delay at signal exchange - max | 0 ms | ||
10.2.3.3 resist. of insul. mat. to abnormal heat/fire by internal elect. effects | meets the product standard's requirements. | ||
10.2.3.2 verification of resistance of insulating materials to normal heat | meets the product standard's requirements. | ||
data transfer rate | 250 kbit/s, smartwire-dt setting automatically |
||
air discharge | 8 kv, according to iec 61131-2, level 3, esd | ||
height of fall (iec/en 60068-2-32) - max | .3 m | ||
supply voltage at ac, 60 hz - min | 0 vac | ||
short-circuit protection | 4 a gl/gg, relay outputs, external | ||
heat dissipation per pole, current-dependent pvid | 0 w | ||
10.13 mechanical function | the device meets the requirements, provided the information in the instruction leaflet (il) is observed. | ||
permitted voltage at output - min | 0 v | ||
supply voltage at dc - max | 28.8 vdc | ||
10.5 protection against electric shock | does not apply, since the entire switchgear needs to be evaluated. | ||
10.9.3 impulse withstand voltage | is the panel builder's responsibility. | ||
lifespan, electrical | 50,000 operations (at 250 v, ac-1, 4 a) 50,000 operations (at 250 v, ac-15, 3 a) 200,000 operations (at 24 v, dc-13, 1 a) |
||
climatic proofing | damp heat, constant, to iec 60068-2-3 dry heat to iec 60068-2-2 |
||
supply voltage at dc - min | 0 vdc | ||
10.8 connections for external conductors | is the panel builder's responsibility. | ||
10.12 electromagnetic compatibility | is the panel builder's responsibility. | ||
Shock resistance | 15 g, mechanical, according to iec/en 60068-2-27, half-sinusoidal shock 11 ms, 9 impacts | ||
Environmental conditions | condensation: prevent with appropriate measures | ||
10.2.4 resistance to ultra-violet (uv) radiation | meets the product standard's requirements. | ||
data transmission type | relay | ||
Type | digital modules | ||
sil (iec 61508) | none | ||
ambient storage temperature - max | 70 °c | ||
Overvoltage category | ii | ||
Protocol | other bus systems | ||
electromagnetic fields | 3 v/m at 1.4 - 2 ghz (according to iec/en 61131-2:2008) 10 v/m at 80 - 1000 mhz (according to iec/en 61131-2:2008) 1 v/m at 2.0 - 2.7 ghz (according to iec/en 61131-2:2008) |
||
pick-up time | 5 ms | ||
load current | min. 100 ma (at 12 v dc) | ||
heat dissipation capacity pdiss | 0 w | ||
radio interference class | class a (en 55011) | ||
product category | smartwire-dt slave | ||
voltage type | ac | ||
10.3 degree of protection of assemblies | meets the product standard's requirements. | ||
10.6 incorporation of switching devices and components | does not apply, since the entire switchgear needs to be evaluated. | ||
ambient operating temperature - min | -25 °c | ||
permitted voltage at input - min | 20.4 v | ||
Features | fieldbus connection over separate bus coupler possible | ||
ambient operating temperature - max | 55 °c | ||
system accessory | yes | ||
limit value type 1 | low: < 5 v dc high: > 15 v dc |
||
ambient storage temperature - min | -40 °c | ||
air pressure | 795 - 1080 hpa (operation) | ||
mounting method | rail mounting possible wall mounting/direct mounting top-hat rail fixing (according to iec/en 60715, 35 mm) |
||
10.11 short-circuit rating | is the panel builder's responsibility. | ||
radiated rfi | 10 v (iec/en 61131-2:2008, level 3) | ||
certifications | csa file no.: 2324643 ul file no.: e29184 iec/en 61131-2 ul category control no.: nkcr csa class no.: 3211-07 csa ul |
||
product width | 35 mm | ||
product length/depth | 102 mm |
explosion safety category for dust | none | ||
10.10 temperature rise | the panel builder is responsible for the temperature rise calculation. eaton will provide heat dissipation data for the devices. | ||
10.7 internal electrical circuits and connections | is the panel builder's responsibility. | ||
relative humidity | 5 - 95 % (non-condensing, iec/en 60068-2-30) | ||
connection type | connection plug: external device plug swd4-8sf2-5, smartwire-dt plug, 8-pole, smartwire-dt push in terminals, supply and i/o sensor |
||
operating temperature - max | 55 °c | ||
number of outputs (digital) | 2 | ||
contact type | n/o contact, relay output | ||
equipment heat dissipation, current-dependent pvid | 0 w | ||
operating temperature - min | -25 °c | ||
drop and topple | 50 mm drop height, drop to iec/en 60068-2-31 | ||
safety performance level (en iso 13849-1) | none | ||
10.9.4 testing of enclosures made of insulating material | is the panel builder's responsibility. | ||
electric connection type | flat plug-in connection | ||
Mounting position | as required | ||
safe isolation | 230 v ac, according to en 50178 | ||
number of inputs (digital) | 4 | ||
static heat dissipation, non-current-dependent pvs | 1 w | ||
connection to smartwire-dt | yes | ||
permitted voltage at output - max | 250 v | ||
contact discharge | 4 kv, according to iec/en 61131-2, level 2, esd | ||
10.2.5 lifting | does not apply, since the entire switchgear needs to be evaluated. | ||
Input current | 4 ma (at 24 v dc, digital inputs) | ||
Current consumption | 45 ma, smartwire-dt network | ||
10.2.7 inscriptions | meets the product standard's requirements. | ||
input delay | < 0.2 ms | ||
10.2.2 corrosion resistance | meets the product standard's requirements. | ||
functions | for connection of digital i/o signals | ||
Pollution degree | 2 | ||
Degree of protection | ip20 | ||
10.9.2 power-frequency electric strength | is the panel builder's responsibility. | ||
output current | 3 a | ||
output | 2 relay outputs | ||
power loss | 1 w | ||
constant acceleration | 1 g, 8.4 - 150 hz, according to iec/en 61131-2, vibrations | ||
terminal capacity | 0.25 - 1.5 mm² (24 - 16 awg), flexible with ferrule, terminal for i/o sensor 0.2 - 1.5 mm² (awg 24 - 16), solid, terminal for i/o sensor |
||
potential isolation | outputs to smartwire-dt: yes inputs for smartwire-dt: yes output to output: no |
||
category (en 954-1) | none | ||
permitted voltage at input - max | 28.8 v | ||
10.2.6 mechanical impact | does not apply, since the entire switchgear needs to be evaluated. | ||
supply voltage at ac, 60 hz - max | 0 vac | ||
station | smartwire-dt slave, smartwire-dt network | ||
drop-out time | 2.5 ms | ||
input current at signal 1 | 4 ma | ||
explosion safety category for gas | none | ||
constant amplitude | 3,5 mm, 5 - 8.4 hz, according to iec/en 61131-2, vibrations | ||
surge rating | 1 kv, surge i/o cables, surge (iec/en 61131-2:2008, level 1), emc | ||
10.2.3.1 verification of thermal stability of enclosures | meets the product standard's requirements. | ||
led indicator | status indication of relay outputs: yellow led status indication of smartwire-dt network: green led status indication of input: yellow led |
||
10.4 clearances and creepage distances | meets the product standard's requirements. | ||
rated operational current for specified heat dissipation (in) | 0 a | ||
catalog notes | uts 250 vac | ||
Product weight | .1 kg | ||
product height | 90 mm | ||
ean | 4015081161133 |