power consumption (sealing) at dc | 2.3 w | ||
static heat dissipation, non-current-dependent pvs | 2.3 w | ||
code number | 40e | ||
ambient operating temperature - max | 50 °c | ||
screw size | m3.5, terminal screw | ||
rated control supply voltage (us) at ac, 50 hz - max | 0 v | ||
rated control supply voltage (us) at dc - min | 220 v | ||
ambient operating temperature (enclosed) - max | 40 °c | ||
10.2.5 lifting | does not apply, since the entire switchgear needs to be evaluated. | ||
10.12 electromagnetic compatibility | is the panel builder's responsibility. the specifications for the switchgear must be observed. | ||
rated control supply voltage (us) at ac, 50 hz - min | 0 v | ||
10.11 short-circuit rating | is the panel builder's responsibility. the specifications for the switchgear must be observed. | ||
rated operational current for specified heat dissipation (in) | 6 a | ||
certifications | ul file no.: e29184 csa csa file no.: 012528 vde 0660 ul en 60947-5-1 ul category control no.: nkcr iec/en 60947 iec/en 60947-4-1 csa class no.: 3211-03 csa-c22.2 no. 14-05 ce ul 508 |
||
product width | 45 mm | ||
product length/depth | 54 mm | ||
rated insulation voltage (ui) | 690 v | ||
Shock resistance | 8 g, n/c auxiliary contact, basic unit with auxiliary contact module, mechanical, according to iec/en 60068-2-27, half-sinusoidal shock 10 ms 10 g, n/o auxiliary contact, basic unit with auxiliary contact module, mechanical, according to iec/en 60068-2-27, half-sinusoidal shock 10 ms |
||
short-circuit protection rating | 10 a fast, 500v, maximum fuse, short-circuit rating without welding, contacts | ||
rated control supply voltage (us) at ac, 60 hz - max | 0 v | ||
10.2.4 resistance to ultra-violet (uv) radiation | meets the product standard's requirements. | ||
duty factor | 100 % | ||
Tightening torque | 1.2 nm, screw terminals | ||
10.10 temperature rise | the panel builder is responsible for the temperature rise calculation. eaton will provide heat dissipation data for the devices. | ||
power consumption (pick-up) at dc | 2.3 w | ||
10.7 internal electrical circuits and connections | is the panel builder's responsibility. | ||
Pollution degree | 3 | ||
Overvoltage category | iii | ||
control circuit reliability | < 2 λ, < 1 failure at 100,000,000 operations (at uₑ = 24 v dc, umin = 17 v, imin = 5.4 ma) | ||
terminal capacity (solid/stranded awg) | 1 x (18 - 14) 2 x (18 - 14) 18 - 14 |
||
10.2.3.3 resist. of insul. mat. to abnormal heat/fire by internal elect. effects | meets the product standard's requirements. | ||
10.2.3.2 verification of resistance of insulating materials to normal heat | meets the product standard's requirements. | ||
short-circuit protection rating without welding | 6 a gg/gl, 500 v, max. fuse, contacts | ||
pick-up voltage | 0.85 - 1.3 v dc x uc 0.7 - 1.3 v dc x uc (at 24 v: without auxiliary contact module and at ambient air temperature + 40 °c) |
||
heat dissipation capacity pdiss | 0 w | ||
switching time (dc operated, make contacts, closing delay) - max | 35 ms | ||
switching capacity (auxiliary contacts, general use) | 10 a, 600 v ac, (ul/csa) 0.5 a, 250 v dc, (ul/csa) |
||
switching time (dc operated, make contacts, opening delay) - max | 25 ms | ||
rated operational current (ie) at ac-15, 380 v, 400 v, 415 v | 3 a | ||
heat dissipation per pole, current-dependent pvid | .4 w | ||
10.9.4 testing of enclosures made of insulating material | is the panel builder's responsibility. | ||
10.13 mechanical function | the device meets the requirements, provided the information in the instruction leaflet (il) is observed. | ||
Mounting position | as required (except vertical with terminals a1/a2 at the bottom) | ||
10.5 protection against electric shock | does not apply, since the entire switchgear needs to be evaluated. | ||
ambient operating temperature - min | -25 °c | ||
rated control supply voltage (us) at dc - max | 220 v |
rated operational current (ie) at ac-15, 500 v | 1.5 a | ||
Features | positive operating contacts to en 60947-5-1 appendix l, including auxiliary contact module | ||
climatic proofing | damp heat, constant, to iec 60068-2-78 damp heat, cyclic, to iec 60068-2-30 |
||
protection | finger and back-of-hand proof, protection against direct contact when actuated from front (en 50274) | ||
10.8 connections for external conductors | is the panel builder's responsibility. | ||
fitted with: | interlocked opposing contacts | ||
10.2.3.1 verification of thermal stability of enclosures | meets the product standard's requirements. | ||
stripping length (main cable) | 8 mm | ||
mounting method | din-rail/screw | ||
10.4 clearances and creepage distances | meets the product standard's requirements. | ||
ambient operating temperature (enclosed) - min | 25 °c | ||
terminal capacity (flexible with ferrule) | 1 x (0.75 - 1.5) mm² 2 x (0.75 - 1.5) mm² |
||
switching time (dc operated, make contacts, opening delay) - min | 15 ms | ||
Product weight | .206 kg | ||
product height | 58 mm | ||
ean | 4015080103035 | ||
switching capacity (auxiliary contacts, pilot duty) | a600, ac operated (ul/csa) p300, dc operated (ul/csa) |
||
number of auxiliary contacts (normally open contacts) | 4 | ||
number of contacts (normally open contacts) | 4 | ||
10.2.7 inscriptions | meets the product standard's requirements. | ||
10.2.2 corrosion resistance | meets the product standard's requirements. | ||
screwdriver size | 2, terminal screw, pozidriv screwdriver 0.8 x 5.5/1 x 6 mm, terminal screw, standard screwdriver |
||
conventional thermal current ith at 50°c (3-pole, open) | 10 a | ||
rated impulse withstand voltage (uimp) | 6000 v ac | ||
switching time (dc operated, n/o, with auxiliary contact module, closing delay) | 70 ms | ||
rated control supply voltage (us) at ac, 60 hz - min | 0 v | ||
rated operational voltage (ue) at ac - max | 600 v | ||
Degree of protection | ip20 | ||
10.9.2 power-frequency electric strength | is the panel builder's responsibility. | ||
lifespan, mechanical | 20,000,000 operations (dc operated) | ||
switching time (dc operated, make contacts, closing delay) - min | 26 ms | ||
terminal capacity (solid) | 1 x (0.75 - 2.5) mm² 2 x (0.75 - 2.5) mm² |
||
connection type (auxiliary circuit) | screw connection | ||
rated operational current (ie) | 0.5 a at 220 v, dc l/r ≤ 15 ms (with 3 contacts in series) 2.5 a at 24 v, dc l/r ≤ 15 ms (with 1 contact in series) 2.5 a at 60 v, dc l/r ≤ 15 ms (with 2 contacts in series) 1.5 a at 110 v, dc l/r ≤ 15 ms (with 3 contacts in series) |
||
equipment heat dissipation, current-dependent pvid | 0 w | ||
product category | diler mini-contactors | ||
voltage type | dc | ||
operating frequency | 9000 operations/h | ||
Application | contactor relays | ||
10.3 degree of protection of assemblies | does not apply, since the entire switchgear needs to be evaluated. | ||
10.2.6 mechanical impact | does not apply, since the entire switchgear needs to be evaluated. | ||
rated operational current (ie) at ac-15, 220 v, 230 v, 240 v | 6 a | ||
safe isolation | 300 v ac, between coil and auxiliary contacts, according to en 61140 300 v ac, between auxiliary contacts, according to en 61140 |
||
10.6 incorporation of switching devices and components | does not apply, since the entire switchgear needs to be evaluated. | ||
10.9.3 impulse withstand voltage | is the panel builder's responsibility. | ||
voltage tolerance | smoothed dc, three-phase bridge rectifiers or smoothed double-wave rectification |
Stock | 9 uds. |
---|---|
Referencia | 010303 |
Fabricante | EATON |
Unidades | Precio / Unidad |
---|---|
1 - 4 | $224,69 |
5+ | $220,20 |