| power consumption (sealing) at dc | 2.3 w | ||
| static heat dissipation, non-current-dependent pvs | 2.3 w | ||
| code number | 40e | ||
| ambient operating temperature - max | 50 °c | ||
| screw size | m3.5, terminal screw | ||
| rated control supply voltage (us) at ac, 50 hz - max | 0 v | ||
| rated control supply voltage (us) at dc - min | 220 v | ||
| ambient operating temperature (enclosed) - max | 40 °c | ||
| 10.2.5 lifting | does not apply, since the entire switchgear needs to be evaluated. | ||
| 10.12 electromagnetic compatibility | is the panel builder's responsibility. the specifications for the switchgear must be observed. | ||
| rated control supply voltage (us) at ac, 50 hz - min | 0 v | ||
| 10.11 short-circuit rating | is the panel builder's responsibility. the specifications for the switchgear must be observed. | ||
| rated operational current for specified heat dissipation (in) | 6 a | ||
| certifications | ul file no.: e29184 csa csa file no.: 012528 vde 0660 ul en 60947-5-1 ul category control no.: nkcr iec/en 60947 iec/en 60947-4-1 csa class no.: 3211-03 csa-c22.2 no. 14-05 ce ul 508 |
||
| product width | 45 mm | ||
| product length/depth | 54 mm | ||
| rated insulation voltage (ui) | 690 v | ||
| Resistencia a los golpes | 8 g, n/c auxiliary contact, basic unit with auxiliary contact module, mechanical, according to iec/en 60068-2-27, half-sinusoidal shock 10 ms 10 g, n/o auxiliary contact, basic unit with auxiliary contact module, mechanical, according to iec/en 60068-2-27, half-sinusoidal shock 10 ms |
||
| short-circuit protection rating | 10 a fast, 500v, maximum fuse, short-circuit rating without welding, contacts | ||
| rated control supply voltage (us) at ac, 60 hz - max | 0 v | ||
| 10.2.4 resistance to ultra-violet (uv) radiation | meets the product standard's requirements. | ||
| duty factor | 100 % | ||
| Par de apriete | 1.2 nm, screw terminals | ||
| 10.10 temperature rise | the panel builder is responsible for the temperature rise calculation. eaton will provide heat dissipation data for the devices. | ||
| power consumption (pick-up) at dc | 2.3 w | ||
| 10.7 internal electrical circuits and connections | is the panel builder's responsibility. | ||
| Grado de ensuciamiento | 3 | ||
| Overvoltage category | iii | ||
| control circuit reliability | < 2 λ, < 1 failure at 100,000,000 operations (at uₑ = 24 v dc, umin = 17 v, imin = 5.4 ma) | ||
| terminal capacity (solid/stranded awg) | 1 x (18 - 14) 2 x (18 - 14) 18 - 14 |
||
| 10.2.3.3 resist. of insul. mat. to abnormal heat/fire by internal elect. effects | meets the product standard's requirements. | ||
| 10.2.3.2 verification of resistance of insulating materials to normal heat | meets the product standard's requirements. | ||
| short-circuit protection rating without welding | 6 a gg/gl, 500 v, max. fuse, contacts | ||
| pick-up voltage | 0.85 - 1.3 v dc x uc 0.7 - 1.3 v dc x uc (at 24 v: without auxiliary contact module and at ambient air temperature + 40 °c) |
||
| heat dissipation capacity pdiss | 0 w | ||
| switching time (dc operated, make contacts, closing delay) - max | 35 ms | ||
| switching capacity (auxiliary contacts, general use) | 10 a, 600 v ac, (ul/csa) 0.5 a, 250 v dc, (ul/csa) |
||
| switching time (dc operated, make contacts, opening delay) - max | 25 ms | ||
| rated operational current (ie) at ac-15, 380 v, 400 v, 415 v | 3 a | ||
| heat dissipation per pole, current-dependent pvid | .4 w | ||
| 10.9.4 testing of enclosures made of insulating material | is the panel builder's responsibility. | ||
| 10.13 mechanical function | the device meets the requirements, provided the information in the instruction leaflet (il) is observed. | ||
| Posición de montaje | as required (except vertical with terminals a1/a2 at the bottom) | ||
| 10.5 protection against electric shock | does not apply, since the entire switchgear needs to be evaluated. | ||
| ambient operating temperature - min | -25 °c | ||
| rated control supply voltage (us) at dc - max | 220 v |
| rated operational current (ie) at ac-15, 500 v | 1.5 a | ||
| Features | positive operating contacts to en 60947-5-1 appendix l, including auxiliary contact module | ||
| climatic proofing | damp heat, constant, to iec 60068-2-78 damp heat, cyclic, to iec 60068-2-30 |
||
| protection | finger and back-of-hand proof, protection against direct contact when actuated from front (en 50274) | ||
| 10.8 connections for external conductors | is the panel builder's responsibility. | ||
| fitted with: | interlocked opposing contacts | ||
| 10.2.3.1 verification of thermal stability of enclosures | meets the product standard's requirements. | ||
| stripping length (main cable) | 8 mm | ||
| mounting method | din-rail/screw | ||
| 10.4 clearances and creepage distances | meets the product standard's requirements. | ||
| ambient operating temperature (enclosed) - min | 25 °c | ||
| terminal capacity (flexible with ferrule) | 1 x (0.75 - 1.5) mm² 2 x (0.75 - 1.5) mm² |
||
| switching time (dc operated, make contacts, opening delay) - min | 15 ms | ||
| Peso del producto | .206 kg | ||
| product height | 58 mm | ||
| ean | 4015080103035 | ||
| switching capacity (auxiliary contacts, pilot duty) | a600, ac operated (ul/csa) p300, dc operated (ul/csa) |
||
| number of auxiliary contacts (normally open contacts) | 4 | ||
| number of contacts (normally open contacts) | 4 | ||
| 10.2.7 inscriptions | meets the product standard's requirements. | ||
| 10.2.2 corrosion resistance | meets the product standard's requirements. | ||
| screwdriver size | 2, terminal screw, pozidriv screwdriver 0.8 x 5.5/1 x 6 mm, terminal screw, standard screwdriver |
||
| conventional thermal current ith at 50°c (3-pole, open) | 10 a | ||
| rated impulse withstand voltage (uimp) | 6000 v ac | ||
| switching time (dc operated, n/o, with auxiliary contact module, closing delay) | 70 ms | ||
| rated control supply voltage (us) at ac, 60 hz - min | 0 v | ||
| rated operational voltage (ue) at ac - max | 600 v | ||
| Grado de protección | ip20 | ||
| 10.9.2 power-frequency electric strength | is the panel builder's responsibility. | ||
| lifespan, mechanical | 20,000,000 operations (dc operated) | ||
| switching time (dc operated, make contacts, closing delay) - min | 26 ms | ||
| terminal capacity (solid) | 1 x (0.75 - 2.5) mm² 2 x (0.75 - 2.5) mm² |
||
| connection type (auxiliary circuit) | screw connection | ||
| rated operational current (ie) | 0.5 a at 220 v, dc l/r ≤ 15 ms (with 3 contacts in series) 2.5 a at 24 v, dc l/r ≤ 15 ms (with 1 contact in series) 2.5 a at 60 v, dc l/r ≤ 15 ms (with 2 contacts in series) 1.5 a at 110 v, dc l/r ≤ 15 ms (with 3 contacts in series) |
||
| equipment heat dissipation, current-dependent pvid | 0 w | ||
| product category | diler mini-contactors | ||
| voltage type | dc | ||
| operating frequency | 9000 operations/h | ||
| Aplicación | contactor relays | ||
| 10.3 degree of protection of assemblies | does not apply, since the entire switchgear needs to be evaluated. | ||
| 10.2.6 mechanical impact | does not apply, since the entire switchgear needs to be evaluated. | ||
| rated operational current (ie) at ac-15, 220 v, 230 v, 240 v | 6 a | ||
| safe isolation | 300 v ac, between coil and auxiliary contacts, according to en 61140 300 v ac, between auxiliary contacts, according to en 61140 |
||
| 10.6 incorporation of switching devices and components | does not apply, since the entire switchgear needs to be evaluated. | ||
| 10.9.3 impulse withstand voltage | is the panel builder's responsibility. | ||
| voltage tolerance | smoothed dc, three-phase bridge rectifiers or smoothed double-wave rectification |
| Stock | 25 uds. |
|---|---|
| Referencia | 010303 |
| Fabricante | EATON |
| Unidades | Precio / Unidad |
|---|---|
| 1+ | 49,06 € |
Las cookies son pequeños archivos de texto que pueden mejorar la experiencia del usuario en los sitios web
La ley estipula que podemos almacenar las cookies estrictamente necesarias en su dispositivo para el correcto funcionamiento de este sitio. Para otros tipos de cookies, requerimos su permiso. Esto significa que las cookies necesarias se procesan según el art. 6 (1) (f), mientras que todas las demás cookies, como las de las categorías de preferencias y marketing, se procesan según el art. 6 (1) (a) RGPD.
cookies.cookies_about_type
Tiene la opción de cambiar o retirar su consentimiento en cualquier momento a través de la Declaración de cookies en nuestra sitio web.
Encuentre más información sobre nuestra identidad, cómo contactarnos y nuestras prácticas de procesamiento de datos personales en nuestra Política de Privacidad.