rated insulation voltage (ui) | 440 v | ||
rated fault current - min | .3 a | ||
surge current capacity | 5 ka | ||
10.2.4 resistance to ultra-violet (uv) radiation | meets the product standard's requirements. | ||
Type | pfr2 residual current relay type u |
||
10.10 temperature rise | the panel builder is responsible for the temperature rise calculation. eaton will provide heat dissipation data for the devices. | ||
connectable conductor cross section (multi-wired) - min | 1.5 mm² | ||
Pollution degree | 2 | ||
rated short-time withstand current (icw) | 10 ka | ||
connectable conductor cross section (solid-core) - max | 35 mm² | ||
voltage rating | 230 v ac / 400 v ac | ||
10.2.3.3 resist. of insul. mat. to abnormal heat/fire by internal elect. effects | meets the product standard's requirements. | ||
busbar material thickness | 0.8 mm - 2 mm | ||
heat dissipation capacity | 0 w | ||
built-in width (number of units) | 70 mm (4 su) | ||
leakage current type | a | ||
voltage type | ac | ||
10.9.4 testing of enclosures made of insulating material | is the panel builder's responsibility. | ||
10.13 mechanical function | the device meets the requirements, provided the information in the instruction leaflet (il) is observed. | ||
10.5 protection against electric shock | does not apply, since the entire switchgear needs to be evaluated. | ||
10.6 incorporation of switching devices and components | does not apply, since the entire switchgear needs to be evaluated. | ||
terminal capacity (solid wire) | 1.5 mm² - 35 mm² | ||
10.9.3 impulse withstand voltage | is the panel builder's responsibility. | ||
lifespan, electrical | 4000 operations | ||
built-in depth | 69.5 mm | ||
heat dissipation per pole, current-dependent | 0 w | ||
sensitivity type | pulse-current sensitive | ||
terminal protection | finger and hand touch safe, dguv vs3, en 50274 | ||
10.8 connections for external conductors | is the panel builder's responsibility. | ||
tripping time | 40 ms delayed - selective switch off | ||
test circuit range | 184 v ac - 440 v ac | ||
10.2.5 lifting | does not apply, since the entire switchgear needs to be evaluated. | ||
mounting method | din rail quick attachment with 2 latch positions on top-hat rail iec/en 60715 |
||
10.4 clearances and creepage distances | meets the product standard's requirements. | ||
10.11 short-circuit rating | is the panel builder's responsibility. the specifications for the switchgear must be observed. | ||
compliances | rohs conform | ||
product width | 70 mm | ||
product length/depth | 80 mm |
rated operational voltage (ue) - max | 400 v | ||
permitted storage and transport temperature - max | 60 °c | ||
10.2.7 inscriptions | meets the product standard's requirements. | ||
10.2.2 corrosion resistance | meets the product standard's requirements. | ||
connectable conductor cross section (multi-wired) - max | 16 mm² | ||
rated impulse withstand voltage (uimp) | 4 kv | ||
10.7 internal electrical circuits and connections | is the panel builder's responsibility. | ||
accessories required | z-hk 248432 | ||
Degree of protection | ip20 ip20, ip40 with suitable enclosure |
||
10.9.2 power-frequency electric strength | is the panel builder's responsibility. | ||
lifespan, mechanical | 20000 operations | ||
10.2.3.2 verification of resistance of insulating materials to normal heat | meets the product standard's requirements. | ||
width in number of modular spacings | 4 | ||
terminals (top and bottom) | twin-purpose terminals | ||
frame | 45 mm | ||
terminal capacity (stranded cable) | 16 mm² (2x) | ||
10.3 degree of protection of assemblies | does not apply, since the entire switchgear needs to be evaluated. | ||
10.2.6 mechanical impact | does not apply, since the entire switchgear needs to be evaluated. | ||
used with | klv-tc-4 276241 (compact enclosure) z-rc/ak-4te 101062 (sealing cover set) pfr2 residual current relay type u |
||
rated short-circuit strength | 5 ka | ||
ambient operating temperature - min | -25 °c | ||
number of poles | four-pole | ||
connectable conductor cross section (solid-core) - min | 1.5 mm² | ||
Features | selective protection residual current relay additional equipment possible |
||
climatic proofing | 25-55 °c / 90-95% relative humidity according to iec 60068-2 | ||
ambient operating temperature - max | 60 °c | ||
special features | ambient temperature hint: starting at 40 °c, the max. permissible continuous current decreases by 3% for every 1 °c tripping signal contact for subsequent installation z-nhk 248434 |
||
fault current rating | 300 ma | ||
frequency rating | 50 hz | ||
10.2.3.1 verification of thermal stability of enclosures | meets the product standard's requirements. | ||
rated fault current - max | .3 a | ||
amperage rating | 25 a | ||
10.12 electromagnetic compatibility | is the panel builder's responsibility. the specifications for the switchgear must be observed. | ||
permitted storage and transport temperature - min | -35 °c | ||
rated operational current for specified heat dissipation (in) | 25 a | ||
Product weight | .296 kg | ||
product height | 76 mm | ||
ean | 4015082358686 |